BS2-IO-1 modules each allow up to 8 external sensors and actuators to be connected. The modules can be used for sequential circuit. For instance, fans can be switched off. All activities and functions can be remote-controlled and manually controlled via the IO module’s push buttons.
- Mains connection 230 V, 50 Hz with Europlug and 1.5 m connection cable.
- Power supply unit for the system electronics. Microfuse, T 2.5 A, replaceable via front side.
- LEDs for displaying operational data.
- Push buttons for manual operation.
- Plastic casing 250 mm x 110 mm, 85 mm height. Protection class II, protection rating IP40.
- Modules permanently store data, even in the event of a power failure.
- Real-time clock with leap year correction and switches to daylight saving/standard time. Initial charge time of the buffer capacitor 30 minutes, discharge time 31 days.
- Galvanically isolated CAN bus connections with plug-in screw terminals.
- Data cable: Twisted pair 1 x 2 x 0.34 mm², 120 Ω, shielded. Length between modules up to 100 m.
- 8 galvanically isolated inputs (24 V DC) according to EN 61131-2 (Type 1) for external sensors. Connections with plug-in screw terminals.
- 8 galvanically isolated outputs (24 V DC / 0.6 A) according to EN 61131-2 for external actuators. Connections with plug-in screw terminals.
- 24 V DC for inputs and outputs on site.
- Operation manual WiNet-SW-01 Software(2019-06) (DE)
- Installation and operating manual BS2-IO-01(2017-09) (DE)
- User manual BS2 communication system, 7.1(2019-04) (EN)
- Operation manual WiNet-SW-01 Software(2019-06) (DE)
- Installation and operating manual BS2-IO-01(2017-09) (DE)
- User manual BS2 communication system, 7.1(2019-04) (EN)