Minimising health risks posed by hazardous substances whilst ensuring fire safety places a particular legal and moral responsibility on building operators, planners, plant engineers and maintenance companies.
The GefStoffV is a key instrument in German occupational health and safety, designed to systematically minimise health risks posed by hazardous substances and to ensure the safety of employees. The VDI 6202 Part 3.1 guideline guides you through the process of identifying the hazardous substance asbestos in fire dampers, implementing the necessary safety measures and ensuring fire safety through proper maintenance.
Frequently asked questions about fire dampers containing asbestos
A clear determination can be made on the basis of construction documents, years of installation or material analyses. Fire dampers bearing the CE mark or holding a general building authority approval under series Z-41.3 are asbestos-free. Fire dampers with a PA-X number or from earlier periods of use must be examined more closely.
A health risk arises when asbestos fibres are released and enter the ventilation system or the work area. This can affect both building users and people who inspect, test or maintain fire dampers. The possibility of fibres being released cannot be ruled out even when simply opening an access panel.
Following the assessment, each fire damper is individually recorded and the urgency of any refurbishment is evaluated. This involves examining the condition of the components containing asbestos. The worst rating for any single component determines the overall classification. The assessment is carried out by a hazardous substances expert and relates exclusively to asbestos; it does not take into account the structural or fire safety characteristics of the building.
Work on fire dampers containing asbestos is subject to a notification requirement and a requirement for specialist knowledge. Before work commences, the employer must carry out a risk assessment and specify the necessary safety and protective measures. In doing so, the requirements of the Hazardous Substances Ordinance and TRGS 519 must be taken into account.
The procedure depends on the urgency of the remediation work identified. For urgency level I, the flap must not be released. For urgency levels II and III, low-emission or project-specific testing methods are permitted. As asbestos fibres may be released when the flap is released, appropriate protective measures are required.
No. Permanent decommissioning is not permitted, as this would mean the end of the intended service life. The fire damper must be professionally removed and replaced. The necessary fire protection must then be restored.